Voltage
and Current (Amperes)
An
AC Generator is designed to produce a voltage level suitable for the load to
which it is connected. The Generator control circuits are designed to
automatically maintain this voltage level as the load is increased or
decreased. Sudden large changes in loading will produce temporary changes in the
voltage. The Automatic Voltage Regulator (AVR) is
designed
to recover to a stable condition as quickly as possible. The current drawn from
the AC Generator is determined by the amount of load connected to it. Current
creates a temperature rise in the windings, hence the requirement for drawing
air through the AC Generator by means of the cooling fan. If the full load
rated current is exceeded on any phase of the main stator windings, it will
result in overheating in this winding. Similarly, any
restriction
in the flow of air through the machine will result in a rapid increase in the
temperature of the windings.
Frequency
(Hz) and Speed (RPM)
An
AC Generator is a constant speed device, and should not be operated at speeds
above 4% of the rated speed, or more than 1% below the rated speed.
Load
changes will create temporary changes in the speed, but the engine must be
capable of returning to the steady state condition within a few seconds.
The
shaft speed requirements for the AC Generator are determined by:-
(a)
The frequency, (Hz), requirements of the load
(b)
The number of poles, ( main rotors), in the generator
Frequency (HZ)=( N (speed) X P (pairs of poles ))\ (60 (sec’s))
Kilowatts
(kW) kilo Volt Amperes (kVA) and Power Factors (pf.)
For
an AC Generator to supply power for a load of 1kW, the prime mover (engine)
driving the alternator must produce approximately 1.5 horsepower.
Kilowatts
are calculated by the formula: -
kW =(Volts x Amperes x Power Factor)\ (100)
kVA
(kilo Volt Amperes), are calculated by the formula:-
kVA ==(Volts x Amperes)\ (100)
Both
equations are multiplied by _3 (1.732) for a 3 phase machine.
Power
Factor
The
Power Factor (pf), is a measure of wasted current, which is a product of
inductive loads such as motors, transformers, (magnetic circuits), and some
forms of lighting.
The
formula for calculating the Power Factor is:-
pf = (kiloWatts) \ (kVA)
Unity
Power Factor (pf 1)
Purely
resistive load, i.e. heating, tungsten filament lighting, has a power factor of
one, (pf1), and contains very little Wattless (inductive) load, which is power
factor zero, (pf 0).
An
AC Generator will deliver continuously the rated full load current at any power
factor between pf1 (unity) and 0.8. However, the prime mover, (engine), is
greatly affected by the power factor. At pf1, the kVA and kW are equal;
therefore the engine is supplying 20% more kW load at pf1, than at pf 0.8. It
is important, therefore, that this is taken into consideration, when
approaching 75% to 100% load current of the Generator, with a power factor higher
than 0.8.
Lagging
Power Factors
A
Generator is designed to deliver the full load current at any power factor
between unity and 0.8 lagging. Certain loads have a power factor lower than 0,8
lag, e.g. welding transformers; autotransformer, motor starting, gas discharge
lighting. A
reduction
in the full load (kVA), rating is required for a continuous lagging pf lower
than 0.8.
Leading
Power Factors
Capacitive
load e.g. some fluorescent lighting, and power factor correction capacitor
banks, produce leading power factor current. The latter is required by the
Electricity authorities to improve the customers lagging power factor. The
capacitor bank size is
measured
in kVAr (reactive). A purely Capacitive load can cause the Generator control
system,
(AVR),
to loose control, creating voltage instability, and possible high voltage from
the Generator. This is due to the fact that, unlike most loads, which are pf1, (unity)
or lagging pf, a leading pf load current will cause the Generator excitation
voltage to decrease, as the load current increases. Eventually the control
system will be unable to control the
Generator
excitation level, and voltage instability will occur. The degree of instability
is determined by the kVAr size of the capacitors, relative to the kVA size of
the alternator. Capacitive load can present a problem for mains failure
(standby) Generators. When the mains electricity supply fails, all motor,
(inductive),
load is disconnected by the individual contactors.
Subsequently,
when the Generator is connected to the system,
the
load will mainly consist of lighting, and possibly power factor
correction
capacitors. In this situation the AC Generator will see a
very
low, (leading), power factor, and may become unstable, and/or generate high
voltage.
In
order to prevent this situation, it is advisable to ensure that the power
factor correction capacitors are switched OFF when the generator takes the
initial load.
Further
advice in this respect may be obtained from Cummins Generator Technologies if
required.
0 comments:
Post a Comment