- Principle of earthing
The path followed by fault current
as the result of a low impedance occurring between the phase conductor and
earthed metal is called the earth fault loop. Current is driven through
the loop impedance by the supply voltage.
The extent of the earth fault loop
for a TT system is shown in
{Fig (1)}, and is made up of the
following labelled parts.
|
l. - the phase conductor from
the transformer to the installation
2. - the protective
device(s) in the installation
3. - the installation
phase conductors from the intake position to the fault
4. - the fault itself (usually
assumed to have zero impedance)
5. - the protective conductor
system
6. - the main earthing terminal
7. - the earthing conductor
8. - the installation earth
electrode
9. - the general mass of earth
10. - the Supply Company's
earth electrode
11. - the Supply Company's
earthing conductor
12. - the secondary
winding of the supply transformer
For a TN-S system (where the
Electricity Supply Company provides an earth terminal), items 8 to 10 are
replaced by the PE conductor, which usually takes the form of the armouring
(and sheath if there is one) of the underground supply cable.
For a TN-C-S system (protective
multiple earthing) items 8 to 11 are replaced by the combined neutral and earth
conductor.
For a TN-C system (earthed
concentric wiring), items 5 to 11 are replaced by the combined neutral and
earth wiring of both the installation and of the supply.
It is readily apparent that the
impedance of the loop will probably be a good deal higher for the TT system,
where the loop includes the resistance of two earth electrodes as well as an
earth path, than for the other methods where the complete loop consists of
metallic conductors.
- The importance of loop impedance
The earth fault loop impedance can
be used with the supply voltage to calculate the earth-fault current.
IF =
|
Uo
|
Zs
|
|
where
|
IF =
fault current, A
|
Uo =
phase voltage, V
|
|
Zs =
loop impedance
|
For example, if a 240 V circuit is
protected by a 15 A semi-enclosed fuse and has an earth-fault loop impedance of
1.6 Ohms, the earth-fault current in the event of a zero impedance earth fault
will he:
IF =
|
Uo =
|
240 A
|
= 150 A
|
Zs
|
1.6
|
This level of earth-fault current
will cause the fuse to operate quickly. From the time taken for the
fuse to operate will be about 0.15 s. Any load current in the circuit will be
additional to the fault current and will cause the fuse to operate slightly
more quickly. However, such load current must not be taken into account when
deciding disconnection time, because it is possible that the load may not be connected
when the fault occurs.
Note that there is no such thing as
a three-phase line/earth fault, although it is possible for three faults to
occur on the three lines to earth simultaneously. As far as calculations for
fault current are concerned, the voltage to earth for standard UK supplies is
always 240 V, for both single-phase and three-phase systems. Thus the Tables of
maximum earth-fault loop impedance .
- The resistance/impedance relationship
Resistance, measured in ohms, is the
property of a conductor to limit the flow of current through it when a voltage
is applied.
I =
|
U
|
|
R
|
||
where
|
I =
|
current,
A
|
U =
|
applied
voltage. V
|
|
R =
|
circuit
resistance, Ohms
|
Thus, a voltage of one volt applied
to a one ohm resistance results in a current of one ampere.
When the supply voltage is
alternating, a second effect, known as reactance (symbol X) is to be
considered. It applies only when the circuit includes inductance and/or
capacitance, and its value, measured in ohms, depends on the frequency of the supply
as well as on the values of the inductance and/or the capacitance concerned.
For almost all installation work the frequency is constant at 50 Hz. Thus,
inductive reactance is directly proportional to inductance and capacitive
reactance is inversely proportional to capacitance.
Xl =
2(pi)fL and Xc =
|
1
|
||
2(pi)fC
|
|||
where
|
Xl =
|
inductive
reactance (Ohms)
|
|
Xc =
|
capacitive
reactance (Ohms)
|
||
(pi)
=
|
the
mathematical constant (3.142)
|
||
f =
|
the
supply frequency (Hz)
|
||
L =
|
circuit
inductance (H)
|
||
C =
|
circuit
capacitance (F)
|
Resistance (R) and reactance (Xl or
Xc) in series add together to produce the circuit impedance (symbol z), but not
in a simple arithmetic manner. Impedance is the effect which limits alternating
current in a circuit containing reactance as well as resistance.
Z =
|
U
|
|
I
|
||
where
|
Z =
|
impedance
(Ohms)
|
U =
|
applied
voltage (V)
|
|
I =
|
current
(A)
|
It follows that a one volt supply
connected across a one ohm impedance results in a current of one ampere.
When resistance and reactance are
added this is done as if they were at right angles, because the current in a
purely reactive circuit is 90° out of phase with that in a purely resistive
circuit. The relationships between resistance, reactance and impedance are:
|
These relationships can be shown in
the form of a diagram applying Pythagoras' theorem as shown in {Fig 5.8}. The
two diagrams are needed because current lags voltage in the inductive circuit,
but leads it in the capacitive. The angle between the resistance R and the
impedance Z is called the circuit phase angle, given the symbol a (Greek
'phi'). If voltage and current are both sinusoidal, the cosine of this angle,
cos a, is the circuit power factor, which is said to be lagging for the
inductive circuit, and leading for the capacitive.
In practice, all circuits have some
inductance and some capacitance associated with them. However, the inductance
of cables only becomes significant when they have a cross-sectional area of 25
mm² and greater. Remember that the higher the earth fault loop impedance the
smaller the fault current will be. Thus, if simple arithmetic is used to add
resistance and reactance, and the resulting impedance is low enough to open the
protective device quickly enough, the circuit will be safe. This is because the
Pythagorean addition will always give lower values of impedance than simple
addition.
For example, if resistance is 2 Ohms
and reactance 1 Ohm, simple arithmetic addition gives
Z
|
= R
+ X – 2 + 1 = 3 Ohms
|
and
correct addition gives
|
|
Z
|
= (R²
+ X²)
|
= (2²
+ 1²) = 5 = 2.24 Ohms
|
If 3 Ohms is acceptable, 2.24 Ohms
will allow a larger fault current to flow which will operate the protective
device more quickly and is thus even more acceptable.
- Earth-fault loop impedance values
The over-riding requirement is that
sufficient fault current must flow in the event of an earth fault to ensure
that the protective device cuts off the supply before dangerous shock can
occur. For normal 240 V systems, there are two levels of maximum disconnection
time. These are:
For socket outlet circuits where
equipment could be tightly grasped: 0.4 s
For fixed equipment where contact is
unlikely to be so good: 5 s
The maximum disconnection time of 5
s also applies to feeders and sub-mains.
It must be appreciated that the
longest disconnection times for protective devices, leading to the longest
shock times and the greatest danger, will be associated with the lowest levels
of fault current, and not, as is commonly believed, the highest levels.
Where the voltage is other than 240
V, [Table 41A] gives a range of disconnection times for socket outlet circuits,
of which the lowest is 0.1 s for voltages exceeding 400 V.
In general, the requirement is that
if a fault of negligible impedance occurs between a phase and earth, the
earth-fault loop impedance must not be greater than the value calculated from..
Zs
<
|
Uo
|
|
Ia
|
||
where
|
Zs =
|
the
earth fault loop impedance (Ohms)
|
Uo =
|
the
system voltage to earth(V)
|
|
Ia =
|
the
current causing automatic disconnection
|
|
(operation
of the protective device) in the required time [A]).
|
depend on the supply voltage and
assume, as shown in the Tables, a value of 240 V. Whilst it would appear that
240 V is likely to be the value of the supply voltage in Great Britain for the
foreseeable future, it is not impossible that different values may apply. In
such a case, the tabulated value for earth fault loop impedance should be
modified using the formula:-
Zs =
|
Zt x
|
U
|
|
U240
|
|||
where
|
Zs =
|
is
the earth fault loop impedance required for safety
|
|
Zt =
|
is
the tabulated value of earth fault loop impedance
|
||
U =
|
is
the actual supply voltage
|
||
U240
=
|
is
the supply voltage assumed in the Table.
|
As an alternative to this
calculation, a whole series of maximum values of earth fault loop impedance i (from
for disconnection within 0.4 s. The reader should not think that these values
are produced in some mysterious way - all are easily verified using the
characteristic curves
For example, consider a 20 A HRC
fuse to BS88 used in a 240 V system. and indicates that disconnection in
0.4 s requires a current of about 130 A. It is difficult (if not impossible) to
be precise about this value of current, because it is between the 100 A and 150
A current graduations.
Using
these values,
|
||||
Zs =
|
Uo
|
=
|
240
|
Ohms
= 1.84 Ohms
|
Ia
|
130
|
Reference to {Table(.1)} shows
that the stated value is 1.8 Oh,s, the discrepancy being due to the difficulty
in reading the current with accuracy. {Tables (.1) and(.2)} give
maximum earth-fault loop impedance values for fuses and for miniature circuit
breakers to give a minimum disconnection time of 0.4 s in the event of a zero
impedance fault from phase to earth.
The reason for the inclusion of
fixed equipment as well as distribution circuits in {Table (2)} will
become apparent later in this sub-section.
Table (1) - Maximum
earth-fault loop impedance for 240 V socket outlet circuits protected by
fuses
|
|||
Fuse rating (A)
|
Maximum earth-fault
loop impedance (Ohms)
|
||
-
|
Cartridge
BS 88 |
Cartridge BS 1361
|
Semi-enclosed BS3036
|
5
|
-
|
10.9
|
10.0
|
6
|
8.89
|
-
|
-
|
10
|
5.33
|
-
|
-
|
15
|
-
|
3.43
|
2.67
|
20
|
1.85
|
1.78
|
1.85
|
30
|
-
|
1.20
|
1.14
|
32
|
1.09
|
-
|
-
|
40
|
0.86
|
-
|
-
|
45
|
-
|
0.60
|
0.62
|
Table (2) - Maximum
earth-fault loop impedance for 240 V circuits
-protected by miniature circuit breakers to give compliance with 0.4 s disconnection time |
|||||
-
|
Maximum earth-fault loop impedance (Ohms)
|
||||
Device rating (A)
|
MCB
type 1 |
MCB
type 2 |
MCB
type 3 and type C |
MCB
type B |
MCB
type D |
5
|
12.00
|
6.86
|
4.80
|
-
|
2.40
|
6
|
10.00
|
5.71
|
4.00
|
8.00
|
2.00
|
10
|
6.00
|
3.43
|
2.40
|
4.80
|
1.20
|
15
|
4.00
|
2.29
|
1.60
|
-
|
0.80
|
16
|
3.75
|
2.14
|
1.50
|
3.00
|
0.75
|
20
|
3.00
|
1.71
|
1.20
|
2.40
|
0.60
|
25
|
2.40
|
1.37
|
0.96
|
1.92
|
0.48
|
30
|
2.00
|
1.14
|
0.80
|
-
|
0.40
|
32
|
1.88
|
1.07
|
0.75
|
1.50
|
0.38
|
40
|
1.5
|
0.86
|
0.60
|
1.20
|
0.30
|
The severity of the electric shock
received when there is a phase to earth fault (indirect contact) depends
entirely on the impedance of the circuit protective conductor. Since this volt
drop is equal to fault current times protective conductor impedance, if the
protective conductor has a lower impedance the shock voltage will he less. Thus
it can be sustained for a longer period without extreme danger.
Socket outlet circuits can therefore
have a disconnection time of up to 5 s provided that the circuit protective
conductor impedance's are no higher than shown in {Table (3)} for various types
of protection.
The reasoning behind this set of
requirements becomes clearer if we take an example. {Table 5.3} shows that a 40
A cartridge fuse to BS 88 must have an associated protective conductor
impedance of no more than 0.29 Ohms if it is to comply. from which we can
see that the current for operation in 5 s is about 170 A. The maximum volt drop
across the conductor (the shock voltage) is thus 170 x 0.29 or 49.3 V.
Table (3) - Maximum
impedance of circuit protective conductors to allow 5 s disconnection
time for socket outlets
|
||||||||
-
|
Maximum impedance of circuit protective conductor
|
|||||||
Rating (A)
|
Fuse BS 88
|
Fuse BS 1361
|
Fuse BS 3036
|
MCB type 1
|
MCB type 2
|
MCB type 3 & C
|
MCB type B
|
MCB type D
|
5
|
-
|
3.25
|
3.25
|
2.50
|
1.43
|
1.00
|
-
|
0.50
|
6
|
2.48
|
-
|
-
|
2.08
|
1.19
|
0.83
|
1.67
|
0.42
|
10
|
1.48
|
-
|
-
|
1.25
|
0.71
|
0.50
|
1.00
|
0.25
|
15
|
-
|
0.96
|
0.96
|
0.83
|
0.48
|
0.33
|
-
|
-
|
16
|
0.83
|
-
|
-
|
0.78
|
0.45
|
0.31
|
0.63
|
0.16
|
20
|
0.55
|
0.55
|
0.63
|
0.63
|
0.36
|
0.25
|
0.50
|
0.12
|
25
|
0.43
|
-
|
-
|
-
|
-
|
-
|
-
|
0.10
|
30
|
-
|
0.36
|
0.43
|
0.42
|
0.24
|
0.17
|
-
|
-
|
32
|
0.34
|
-
|
-
|
0.39
|
0.22
|
0.16
|
0.31
|
0.08
|
40
|
0.26
|
-
|
-
|
0.31
|
0.18
|
0.13
|
0.25
|
0.06
|
45
|
-
|
0.18
|
0.24
|
0.28
|
0.16
|
0.11
|
0.22
|
0.06
|
Table (4) - Maximum earth-fault loop
impedance for 240 V fixed equipment distribution circuits protected by
fuses
|
|||
-
|
Maximum earth-fault loop impedance
|
||
Device rating
(A) |
Cartridge
BS 88 |
Cartridge
BS 1361 |
Semi-enclosed
BS 3036 |
5
|
-
|
17.1
|
-
|
6
|
14.1
|
-
|
-
|
10
|
7.74
|
-
|
-
|
15
|
-
|
5.22
|
5.58
|
16
|
4.36
|
-
|
-
|
20
|
3.04
|
2.93
|
4.00
|
30
|
-
|
1.92
|
2.76
|
32
|
1.92
|
-
|
-
|
40
|
1.41
|
-
|
-
|
45
|
-
|
1.00
|
1.66
|
50
|
1.09
|
-
|
-
|
Application of the same reasoning to
all the figures gives shock voltages of less than 50 V. This limitation on the
impedance of the CPC is of particular importance in TT systems where it is
likely that the resistance of the earth electrode to the general mass of earth
will be high.
The breaking time of 5 s also
applies to fixed equipment, so the earth-fault loop impedance values can be
higher for these circuits, as well as for distribution circuits. For fuses, the
maximum values of earth-fault loop impedance for fixed equipment are given in
{Table (4)}.
No separate values are given for
miniature circuit breakers. will reveal that there is no change at all in
the current causing operation between 0.4 s and 5 s in all cases except the
Type 1. Here, the vertical characteristic breaks off at 4 s, but this makes
little difference to the protection. In this case, the values given in{Table(2)} can
be used for fixed equipment as well as for socket outlet circuits. An
alternative is to calculate the loop impedance as described above.
- Protective conductor impedance
It has been shown in the previous
sub-section how a low-impedance protective conductor will provide safety from
shock in the event of a fault to earth. This method can only be used where it
is certain that the shock victim can never be in contact with conducting
material at a different potential from that of the earthed system in the zone
he occupies. When overcurrent protective devices are used as protection from
electric shock, the protective conductor must be in the same wiring system as,
or in close proximity to, the live conductors. This is intended to ensure that
the protective conductor is unlikely to he damaged in an accident without the
live conductors also being cut.
{Figure (9)} shows a method of
measuring the resistance of the protective conductor, using a line conductor as
a return and taking into account the different cross-sectional areas of the
phase and the protective conductors.
Fig (3)
- Measurement of protective conductor resistance
Taking the cross-sectional area of
the protective conductor as Ap and that of the line (phase or neutral)
conductor as Al , then
Rp =
resistance reading x
|
Al
|
Al +
Ap
|
For example, consider a reading of
0.72 Ohms obtained when measuring a circuit in the way described and having 2.5
mm² line conductors and a 1.5 mm² protective conductor. The resistance of the
protective conductor is calculated from:
Rp
= R x
|
Al
|
= 0.72
x 2.5
|
Ohms
|
Al +
Ap
|
2.5
+ 1.5
|
||
=
|
0.72
x 2.5
|
Ohms
=
|
0.45
Ohms
|
4.0
|
- Maximum circuit conductor length
The complete earth-fault loop path
is made up of a large number of parts as shown in {Fig (1)}, many of which
are external to the installation and outside the control of the installer.
These external parts make up the external loop impedance (Ze). The rest of the
earth-fault loop impedance of the installation consists of the impedance of the
phase and protective conductors from the intake position to the point at which
the loop impedance is required.
Since an earth fault may occur at
the point farthest from the intake position, where the impedance of the circuit
conductors will be at their highest value, this is the point which must be
considered when measuring or calculating the earth-fault loop impedance for the
installation. Provided that the external fault loop impedance value for the
installation is known, total impedance can be calculated by adding the external
Table (5) - Resistance
per metre of copper conductors at 20°C for calculation of
R1 + R2
|
|
Conductor cross-sectional area
(mm²) |
Resistance per metre run
(m ohms / m) |
1.0
|
18.1
|
1.5
|
12.10
|
2.5
|
7.41
|
4.0
|
4.61
|
6.0
|
3.08
|
10.0
|
1.83
|
16.0
|
1.15
|
25.0
|
0.727
|
Note that to allow
for the increase in resistance with increased temperature under fault
conditions the values of {Table 5.5} must be multiplied by 1.2 for p.v.c.
|
impedance to that of the
installation conductors to the point concerned. The combined resistance of the
phase and protective conductors is known as R1+ R2. The same term is sometimes
used for the combined resistance of neutral and protective conductors. In the
vast majority of cases phase and neutral conductors have the same
cross-sectional area and hence the same resistance.
For the majority of installations,
these conductors will be too small for their reactance to have any effect
(below 25 mm² cross-sectional area reactance is very small), so only their
resistance's will be of importance. This can be measured by the method
indicated in {Fig (3)}, remembering that this time we are interested in
the combined resistance of phase and protective conductors, or can be
calculated if we measure the cable length and can find data concerning the
resistance of various standard cables. These data are given here as {Table
(5)}.
The resistance values given in {Table
(5)} are for conductors at 20°C. Under fault conditions the high fault
current will cause the temperature of the conductors to rise and result in an
increase in resistance. To allow for this changed resistance, It should be
mentioned that the practice which has been adopted here of adding impedance and
resistance values arithmetically is not strictly correct. Phasor addition is
the only perfectly correct method since the phase angle associated with
resistance is likely to he different from those associated with impedance, and
in addition impedance phase angles will differ from one another. However, if
the phase angles are similar, and this will be so in the vast majority of cases
where electrical installations are concerned, the error will be acceptably
small.
It is often assumed that higher
conductor temperatures are associated with the higher levels of fault current.
In most cases this is untrue. A lower fault level will result in a longer
period of time before the protective device operates to clear it, and this
often results in higher conductor temperature.
Thanks for providing this informative and comprehensive blog. This is a very interesting article. The example are really beautiful
ReplyDeletechick here http://intertech.com.co/