Main Parts of Building Automation Systems
Building automation is a
programmed, computerized, "intelligent" network of electronic devices
that monitor and control the different systems of a building such as HVAC,
security, fire, or lighting systems. The intent is to create an
intelligent building and reduce energy and maintenance costs.
Controller
The controller is normally one or
more programmable logic controllers (PLC), often with custom programming. PLCs
come in a wide range of sizes and capabilities to control devices that are
common in buildings. Usually the primary and secondary buses are chosen based
on what the PLCs provide.
Most PLCs provide general purpose
feedback loops, as well as digital circuits.
The operation of a building is
typically based on occupancy. Occupancy is defined by time of day schedules to
show when the building's systems are most likely in need of operation.
Override is possible through different means. Some buildings can sense occupancy in their internal spaces by an override
switch or sensor.
Lighting System
Lighting is another automated
service that can be turned on and off with a building automation system based
on time of day, or the occupancy sensors and timers. Operating times can
be set by individual tenants within the building. One typical example is
to turn the lights in a space on for a half hour since the last motion was
sensed. A photocell placed outside a building can sense darkness, and the time
of day, and modulate lights in outer offices and the parking lot.
Heating ,Ventilation and Air Conditioning
(HVAC) System
Climate control in buildings is an important automated service that can
save a lot of energy and thus money if the right technologies and design were
used. For example, the heating system can be turned down automatically
during the night or switched off completely when windows are open during the
day. The building also "considers" its occupants. The night-time
heating control temperature is not simply reduced on a timer basis like in
conventional systems, it is automatically adjusted to the actual utilization
levels and temperatures can automatically be adjusted to the actual weather
conditions. The indoor air quality can be monitored via suitable sensors, and
the climate can be adjusted as required.
Alarm and Security Systems
Many building automation systems have alarm capabilities. It can be programmed to notify someone if an alarm is detected.
Notification can be through a computer, pager, Mobile phone or audible alarm.
-
Common temperature alarms are
Space, Supply Air, Chilled Water Supply and Hot Water Supply.
-
Differential pressure switches can
be placed on the filter to determine if it is dirty.
-
Status alarms are common. If a
mechanical device like a pump is requested to start, and the status input
indicates it is off. This can indicate a failure.
-
Some valve actuators have end
switches to indicate if the valve has opened or not.
-
Carbon monoxide and carbon dioxide
sensors can be used to alarm if levels are too high.
At sites with several buildings,
momentary power failures can cause hundreds or thousands of alarms from
equipment that has shutdown. Some sites are programmed so that critical alarms
are automatically re-sent at varying intervals. For example, a repeating
critical alarm (of an uninterruptible power supply in 'by pass') might resound
at 10 minutes, 30 minutes, and every 2 to 4 hours there after until the alarms
are resolved.
Security systems can also be
interlocked to a building automation system. If occupancy sensors are present,
they can also be used as burglar alarms.
Fire and smoke alarm systems can
be hard-wired to override building automation. For example: if the smoke alarm
is activated, all the outside air dampers close to prevent air coming into the
building, and an exhaust system can isolate the alarmed area and activate an
exhaust fan to move smoke out of the area. Life safety applications are
normally hard-wired to a mechanical device to override building automation
control.
0 comments:
Post a Comment