Monday, December 16, 2013

What is earthing?

- What is earthing?
The whole of the world may be considered as a vast conductor which is at reference (zero) potential. In the UK we refer to this as 'earth' whilst in the USA it is called 'ground'. People are usually more or less in contact with earth, so if other parts which are open to touch become charged at a different voltage from earth a shock hazard exists . The process of earthing is to connect all these parts which could become charged to the general mass of earth, to provide a path for fault currents and to hold the parts as close as possible to earth potential. In simple theory this will prevent a potential difference between earth and earthed parts, as well as permitting the flow of fault current which will cause the operation of the protective systems.
The standard method of tying the electrical supply system to earth is to make a direct connection between the two. This is usually carried out at the supply transformer, where the neutral conductor (often the star point of a three-phase supply) is connected to earth using an earth electrode or the metal sheath and armouring of a buried cable. {Figure (1)} shows such a connection. Lightning conductor systems must be bonded to the installation earth with a conductor no larger in cross-sectional area than that of the earthing conductor.
Fig(1) - Three-phase delta/star transformer
showing earthing arrangements
The advantages of earthing
The practice of earthing is widespread, but not all countries in the world use it.
There is certainly a high cost involved, so there must be some advantages. In fact
there are two. They are:
1. - The whole electrical system is tied to the potential of the general mass of earth and cannot 'float' at another potential. For example, we can be fairly certain that the neutral of our supply is at, or near, zero volts (earth potential) and that the phase conductors of our standard supply differ from earth by 240 volts.
2. - By connecting earth to metalwork not intended to carry current (an extraneous conductive part or a an exposed conductive part) by using a protective conductor, a path is provided for fault current which can be detected and, if necessary, broken. The path for this fault current is shown in {Fig (2)}.
Fig (2) Path for earth fault current (shown by arrows)
- The disadvantages of earthing
The two important disadvantages are:
1. - Cost: the provision of a complete system of protective conductors, earth electrodes, etc. is very expensive.
2. - Possible safety hazard: It has been argued that complete isolation from earth will prevent shock due to indirect contact because there is no path for the shock current to return to the circuit if the supply earth connection is not made (see {Fig 3(a)}). This approach, however, ignores the presence of earth leakage resistance (due to imperfect insulation) and phase-to-earth capacitance (the insulation behaves as a dielectric). In many situations the combined impedance due to insulation resistance and earth capacitive reactance is low enough to allow a significant shock current (see {Fig 3(b)}).
Fig (3) - Danger in an unearthed system
a) apparent safety: no obvious path for shock current
b) actual danger: shock current via stray resistance and capacitance
-  System classification
The electrical installation does not exist on its own; the supply is part of the overall system. Although Electricity Supply Companies will often provide an earth terminal, they are under no legal obligation to do so. As far as earthing types are concerned, letter classifications are used.
The first letter indicates the type of supply earthing.
T  - indicates that one or more points of the Supply are directly earthed (for example, the earthed neutral at the transformer).
I - indicates either that the supply system is not earthed at all, or that the earthing includes a deliberately-inserted impedance, the purpose of which is to limit fault current. This method is not used for public supplies in the UK.
The second letter indicates the earthing arrangement in the installation.
T - all exposed conductive metalwork is connected directly to earth.
N - all exposed conductive metalwork is connected directly to an earthed supply conductor provided by the Electricity Supply Company.
The third and fourth letters indicate the arrangement of the earthed supply conductor system.
S - neutral and earth conductor systems are quite separate.
C - neutral and earth are combined into a single conductor.
A number of possible combinations of earthing systems in common use is indicated in the following subsections.
Protective conductor systems against lightning need to be connected to the installation earthing system to prevent dangerous potential differences. Where a functional earthing system is in use, the protective requirements of the earthing will take precedence over the functional requirements
- TT systems
This arrangement covers installations not provided with an earth terminal by the Electricity Supply Company. Thus it is the method employed by most (usually rural) installations fed by an overhead supply. Neutral and earth (protective) conductors must be kept quite separate throughout the installation, with the final earth terminal connected to an earth electrode  by means of an earthing conductor.
Effective earth connection is sometimes difficult. Because of this, socket outlet circuits must be protected by a residual current device (RCD) with an operating current of 30 mA . {Fig(4)} shows the arrangement of a TT earthing system.
Fig (4) - TT earthing system
- TN-S system
This is probably the most usual earthing system in the UK, with the Electricity Supply Company providing an earth terminal at the incoming mains position. This earth terminal is connected by the supply protective conductor (PE) back to the star point (neutral) of the secondary winding of the supply transformer, which is also connected at that point to an earth electrode. The earth conductor usually takes the form of the armour and sheath (if applicable) of the underground supply cable. The system is shown diagrammatically in {Fig (5)}.
Fig (5) - TN-S earthing system
- TN-C-S system
In this system, the installation is TN-S, with separate neutral and protective conductors. The supply, however, uses a common conductor for both the neutral and the earth. This combined earth and neutral system is sometimes called the 'protective and neutral conductor' (PEN) or the 'combined neutral and earth' conductor (CNE). The system, which is shown diagrammatically in {Fig (6)}, is most usually called the protective multiple earth (PME) system,
Fig(6) - TN-C-S earthing system - protective multiple earthing
- TN-C system
This installation is unusual, because combined neutral and earth wiring is used in both the supply and within the installation itself. Where used, the installation will usually be the earthed concentric system,
- IT system
The installation arrangements in the IT system are the same for those of the TT system However, the supply earthing is totally different. The IT system can have an unearthed supply, or one which is not solidly earthed but is connected to earth through a current limiting impedance.
The total lack of earth in some cases, or the introduction of current limiting into the earth path, means that the usual methods of protection will not be effective. For this reason, IT systems are not allowed in the public supply system in the UK. An exception is in medical situations such as hospitals. Here it is recommended that an IT system is used for circuits supplying medical equipment that is intended to be used for life-support of patients. The method is also sometimes used where a supply for special purposes is taken from a private generator.

0 comments:

Post a Comment