TRANSFORMERS – CONSTRUCTION
A
transformer primarily consists of three basic parts- a primary winding which
receives the electrical energy from the applied voltage source, and a secondary
winding which receives the induced electrical energy and a core which provides
a circuit of low reluctance for magnetic lines of force.
Windings
Windings, primary as well as secondary, are the coils of
conducting wires as a coil of conductors create a higher magnetic flux compared
to the flux created by a single conductor.
Windings
rated for higher voltages with more number of turns are designated as High
Voltage (HV) winding. The windings for lower voltages are called Low Voltage
(LV) winding. The HV winding is composed of many turns of relatively fine
copper wire, while the LV winding is composed of relatively few turns of heavy
copper wire. The current on the HV side will be lower as V-I product is a
constant. Also the HV winding needs better insulation properties to withstand
higher voltages across it. HV also needs more clearance to the core, yoke or
the body.
The
material used for the windings is application specific. Insulated solid copper
wire is used for small power and signal transformers whereas copper or
aluminium rectangular/strip conductors are used for larger power transformers.
RF transformers use Litz so as to minimise losses due to skin effect.
Tappings
(or external connections) may be provided from the intermediate points on the
windings.
Double-wound
transformers use separate primary and secondary windings, while
autotransformers use single winding with tapping.
Winding Insulation
To
ensure that the current travels around the core along the coiled conductor, and
not through a turn-to-turn-short circuit, winding materials are enamelled
thereby providing insulation. In addition, various other methods are used to
provide insulation. The type of insulation has a definite bearing on the size
and operating temperature of the unit.
Currently
four classes of insulations are used
·
Class 130 insulation-system transformers.
·
Class 150 insulation-system transformers.
·
Class 200 insulation-system transformers.
·
Class 220 insulation-system transformers.
When
properly loaded and installed in an ambient not over 40°C, Class 130, Class
150, Class 200 and Class 220 transformers will operate at not more than a 60°C,
80°C, 130°C and 150°C temperature rise on the winding respectively.
The
insulation used for the electrical conductors in a transformer is varnish or
enamel. In larger power transformers the conductors are insulated using
un-impregnated paper / cloth and the assembly is immersed in a tank containing
oil; the transformer oil acts as an insulator and also as a coolant.
·
Coolant
Because
of the resistance of its windings and the hysteresis and eddy currents in the
iron core, a certain amount of the electrical energy delivered to a transformer
is transformed into heat energy. The mechanism must be provided for removing
the heat energy from the transformer and dissipating it into the surrounding
air otherwise, excessively high temperatures may destroy the insulation of the
transformer. To remove the heat generated in a transformer, coolant is used.
Various types of
cooling mechanisms used are
· Self-air–cooled
transformers (or dry-type transformers)
The
windings are surrounded by air at atmospheric pressure. The heat is removed by
natural convection and radiation. Self-air–cooled transformers are used in
systems with 3000-kVA capacity and voltages up to 15,000 V.
· Air-blast–cooled
transformers
In
this type of transformers, the core and windings are enclosed in a metal
enclosure through which air is circulated by means of a blower. These are used
for large power transformers in ratings up to 15,000 kVA and voltages up to
35,000 V.
·
Liquid-immersed, self-cooled transformers:
In
liquid-immersed, self-cooled transformers, the core and windings are immersed
in an insulating liquid and enclosed in a metal tank. Liquid conducts away the
heat from the core to the tank surface and then, the heat is removed by natural
convection and by radiation.
·
Gas-vapor transformers
In
Gas-vapor transformers, the transformer is insulated with a quantity of gas
necessary for start-up, along with a vaporizable liquid which provides
insulation and cooling during operation
·
Shielding
To
avoid any capacitive effect in the transformers (due to the proximity of
primary and secondary windings), an electrostatic shield is used between the
windings. Transformers may be shielded by magnetic or electrostatic shields, or
both to prevent interference from other devices
·
Terminals
Small
transformers have leads brought out of the unit for circuit connections. Larger
transformers may have bolted terminals, bus bars or high-voltage insulated
bushings.
Cores
Any
material inside a coil, used to serve as a form to support it, is called a
core. Cores are made of different materials with permeability ranging from 1 to
over 10000. The higher permeability aid in providing low reluctance path of the
?ux and the ?ux lines mostly con?ne themselves to the core. The permeability of
air is 1 whereas the permeability of common “ferro-magnetic” materials is about
300 for ordinary steel, about 5,000 for 4% silicon transformer steel, and up to
about 100,000 for some nickel-iron-molybdenum alloys. Because such materials
concentrate magnetic flux, they greatly increase the inductance of a coil. Coil
inductance is directly proportional to the square of the number of turns and
also, direct proportional to the permeability of the core. Silicon steel, hot
rolled grain oriented steel, Cold Rolled Grain Oriented (CRGO), etc. are some
of the material used in the form of thin laminations for the core; the
laminations (in the form of E & I, C & I or O) are coated with a layer
of insulating varnish, oxide or phosphate.
Ferrite
cores are best suited for high frequency applications and steel laminations are
best suited for low frequency applications. For lower frequencies, core
material selection is governed by core saturation considerations. Eddy current
losses are low so steel laminations can be considered. For higher frequencies,
core material selection is governed by core loss considerations. Eddy currents
can be significant. In such applications, ferrites are commonly used.
Numeric
Codes representing the power handling ability have been assigned to the cores
by the manufacturers; the assigned number is the product of its window area and
the core cross-section area. The codes are available for laminations, C cores,
pot cores, powder cores, and Toroidal tape-wound cores.
0 comments:
Post a Comment